Ground Bond Testing: How to Check Protective Earth Continuity

How to perform a ground bond test on electrical equipment: why it uses high current, which standards apply and how to interpret the protective earth result.

Ground Bond Testing: How to Check Protective Earth Continuity

A Class I device, whether it is a machine, a control cabinet, a lab power supply or an industrial appliance, relies on a single conductor to protect whoever touches it: the protective earth conductor that bonds the chassis to the installation’s ground. If a line conductor touches the enclosure and that path is intact, the fault current makes the protective device operate. If the path is broken or has a high-resistance joint, the chassis can sit at a dangerous voltage with nothing tripping. The protective earth continuity test, also known as the ground bond test, checks exactly that path. This guide explains what it is, why it is done at high current, which standards require it and how to interpret the result.

Low-current continuity vs. high-current ground bond

A multimeter on continuity or ohms measures with a current of a few milliamps. At that current, a cord with only one good strand left, a loose screw or a lug fitted over paint can give an apparently good reading. The problem shows up during a real fault: hundreds or thousands of amps try to flow through that weak point, which heats up, opens or drops enough voltage to leave the chassis live.

That is why two tests are distinguished:

  • Ground continuity: performed at low current, usually in the range of hundreds of milliamps or less. It confirms the conductor exists and is connected, but does not assess its ability to carry a fault.
  • Ground bond: performed at high current, typically 10 A to 30 A depending on the standard, applied for a defined time. It stresses the joints in a way similar to a fault and reveals poor connections that the low-current test misses.

The high-current test is done at a low open-circuit voltage, so it does not pose a shock hazard, but the current can heat poor contact points. That is exactly what the test is meant to reveal.

Which standards require it

The test appears in most product and machinery safety standards, each with its own current, duration and limit:

  • IEC 60335-1: household and similar electrical appliances.
  • IEC 61010-1: electrical equipment for measurement, control and laboratory use.
  • IEC 62368-1: information technology and audio/video equipment.
  • IEC 60204-1: electrical equipment of machines. The 2016 edition requires verifying the continuity of the protective bonding circuit with a current of at least 10 A for at least 10 s.
  • IEC 62353: recurrent and post-repair testing of medical electrical equipment.
  • NOM-003-SCFI: in Mexico, safety requirements for electrical products, including verification of the grounding circuit.

Product standards commonly specify currents of around 25 A or a multiple of the equipment’s rated current, a limited open-circuit voltage (commonly no more than 12 V) and resistance limits in the range of tenths of an ohm. The exact values, whether the power cord is included in the measurement and the test duration vary between standards and editions, so always take the parameters from the standard and edition that apply to your product.

How to perform the test step by step

  1. Disconnect the equipment from the mains. The test is done without power. The equipment’s own switch may be on so that every part of the circuit is included, but it must never be connected to the installation.
  2. Visual inspection. Check the cord, plug, earth terminals, star washers and bonding jumpers on doors and covers. Many faults are found before measuring anything.
  3. Compensate the leads. If the instrument measures two-wire, zero it with the leads shorted to subtract their resistance. Four-wire (Kelvin) instruments separate the current path from the voltage measurement and eliminate this error.
  4. Connect to the right points. One end goes to the plug’s earth pin or the supply earth terminal; the other to each accessible conductive part that could become live under a fault: chassis, covers, rails, motor frames, cabinet doors.
  5. Apply the current and duration the standard specifies. Record the resistance at each point. Flex the cord during the test to detect broken strands that only make contact in certain positions.
  6. Do the ground bond test before the hipot. If the protective circuit is open, the dielectric test would not have a safe reference.

How to interpret the result

The result is first compared with the standard’s limit, but it pays to estimate what the circuit should read. Copper has a resistivity of about 0.0172 Ω·mm²/m at 20 °C. A 1.5 mm² conductor has roughly 11.5 mΩ per metre, so in a 2 m cord the earth conductor contributes about 23 mΩ. If that equipment reads 150 mΩ, the conductor is not the problem: there is a poor joint somewhere worth locating, even if the value is within the limit.

Symptom Likely cause
High reading on only one cover or door Missing bonding jumper, or the hinge is the only path
Reading changes when the cord is moved Broken strands near the plug or cable gland
High reading across the whole chassis Loose earth screw, lug over paint or no star washer
Reading rises during the test A contact point heating up under the current
Large differences between identical units Variation in the assembly process or surface finish

Anodized, coated or painted surfaces are a common cause of high readings. The bond must be made on bare metal or with hardware designed to pierce the coating, not by relying on contact through the fasteners.

Production testing and in-service testing

In production, the ground bond test is done on every unit, together with the hipot test and, depending on the product, a leakage current measurement. In service, it is repeated after a repair, a wiring modification or a cord replacement, and periodically when the standard or the maintenance program calls for it, as with medical equipment under IEC 62353. On machines, verification to IEC 60204-1 should be done at commissioning and whenever the protective circuit is worked on.

For the results to serve as evidence, record the instrument used and its calibration, the current and time applied, the points measured and the value obtained at each one.

Equipment for the test

You can use a dedicated ground bond tester, an electrical safety analyzer that combines ground bond, hipot and leakage, or a multifunction installation tester for machines. For field checks and quick verifications, a chassis continuity tester is practical, and to complete the safety assessment it is worth measuring leakage current as well with an electrical safety leakage meter.

How we can help

At CreativeIT Group we perform ground continuity tests at real fault current and electrical safety and functional performance assessments of equipment at our Monterrey laboratory, and we rent the instruments so your team can carry out its own checks. Contact us to review the protective circuit of your equipment before a fault puts it to the test.